| 2001-11-07 00:00:00 | ******************** UNSAT *********** |
| | |
| | 1)NOTE: PLEASE NOTE THAT THE RISER |
| | DIAGRAM SUBMITTED SHOWS AN OVERHEAD |
| | SERVICE? PLEASE CLARIFY? PLANS |
| | SHOW NEW SERVICE IN EXISTING ELECTRICAL |
| | ROOM UPSTAIRS, SHOW HOW SERVICE IS |
| | COMING IN THROUGH WALLS AND OTHER SPACE |
| | SHOWN BEHIND SERVICE WALL? |
| | |
| | 2)NOTE: PLEASE NOTE THAT A NEW CAN ONLY |
| | BE ADDED IF ITEMS IN 230-2 ARE MET. |
| | PLANS DO NOT SHOW ENOUGH DETAIL FOR THIS |
| | ? THE EXSITING SERVICE SIZE IS NOT LARGE |
| | ENOUGH? DOES NOT SHOW VOLTAGE? PHASES? |
| | PLEASE NOTE I CANNOT FIND WHERE PLANS DE |
| | TAIL A 2HR SEPARATION BETWEEN EXSITING |
| | AND NEW AREA IN ORDER FOR IT TO BE |
| | CONSIDERED A SEPARTE BLDG FOR A NEW |
| | SERVICE. |
| | |
| | 3)NOTE: PLEASE CALRIFY WHERE NEW METERS |
| | AND DISCONNECTS ARE? PLEASE SEE E-3 |
| | ELEC ROOM ONLY SHOWS HOUSE PANEL? |
| | |
| | 4)NOTE: PLEASE CLARIFY HOW CONDUITS ARE |
| | GOING TO RUN TO TENANTS 1&2. IF THROUGH |
| | STAIRS/EXIT CORRIDOR, THEN REQ`MENTS FOR |
| | FIRE PLAN REVIEW MUST BE SHOWN. PLEASE |
| | SEE FIRE REVIEW FOR THIS. EXT 8497 |
| | |
| | 5)NOTE: PLEASE CLARIFY LOAD FOR NEW |
| | ELEVATOR LOAD ON HOUSE PANEL? SHOWN AS |
| | 1-POLE 20A 1KW LOAD ? |
| | |
| | |
| | 6)NOTE: PLEASE CLARIFY EQUIPMENT GROUND- |
| | ING CONDUCTOR BETWEEN MAINS AND PANELS. |
| | 250-122 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW, IF THERE ARE ANY QUESTIONS,OR |
| | IF A MEETING WOULD LIKE TO BE SET UP TO |
| | GO OVER ANY ITEMS, PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |