Plan Review Notes
Plan Review Notes For Permit 01090052
Permit Number 01090052
Review Stop E
Sequence Number 2
Notes
Date Text
2001-11-07 00:00:00******************** UNSAT ***********
  
 1)NOTE: PLEASE NOTE THAT THE RISER
 DIAGRAM SUBMITTED SHOWS AN OVERHEAD
 SERVICE? PLEASE CLARIFY? PLANS
 SHOW NEW SERVICE IN EXISTING ELECTRICAL
 ROOM UPSTAIRS, SHOW HOW SERVICE IS
 COMING IN THROUGH WALLS AND OTHER SPACE
 SHOWN BEHIND SERVICE WALL?
  
 2)NOTE: PLEASE NOTE THAT A NEW CAN ONLY
 BE ADDED IF ITEMS IN 230-2 ARE MET.
 PLANS DO NOT SHOW ENOUGH DETAIL FOR THIS
 ? THE EXSITING SERVICE SIZE IS NOT LARGE
 ENOUGH? DOES NOT SHOW VOLTAGE? PHASES?
 PLEASE NOTE I CANNOT FIND WHERE PLANS DE
 TAIL A 2HR SEPARATION BETWEEN EXSITING
 AND NEW AREA IN ORDER FOR IT TO BE
 CONSIDERED A SEPARTE BLDG FOR A NEW
 SERVICE.
  
 3)NOTE: PLEASE CALRIFY WHERE NEW METERS
 AND DISCONNECTS ARE? PLEASE SEE E-3
 ELEC ROOM ONLY SHOWS HOUSE PANEL?
  
 4)NOTE: PLEASE CLARIFY HOW CONDUITS ARE
 GOING TO RUN TO TENANTS 1&2. IF THROUGH
 STAIRS/EXIT CORRIDOR, THEN REQ`MENTS FOR
 FIRE PLAN REVIEW MUST BE SHOWN. PLEASE
 SEE FIRE REVIEW FOR THIS. EXT 8497
  
 5)NOTE: PLEASE CLARIFY LOAD FOR NEW
 ELEVATOR LOAD ON HOUSE PANEL? SHOWN AS
 1-POLE 20A 1KW LOAD ?
  
  
 6)NOTE: PLEASE CLARIFY EQUIPMENT GROUND-
 ING CONDUCTOR BETWEEN MAINS AND PANELS.
 250-122
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW, IF THERE ARE ANY QUESTIONS,OR
 IF A MEETING WOULD LIKE TO BE SET UP TO
 GO OVER ANY ITEMS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372