| 2001-09-12 00:00:00 | DENIED |
| | REFERENCE: SPC-94 - FACBC-97 |
| | |
| | 1) PAGES A2.0 & A2.2 DETAIL 3 RESTROOM |
| | PLAN. 3 LAVS REQUIRED IN WOMEN'S REST- |
| | ROOM PER SPC-94 TABLE 407. |
| | 2) PAGE A2.2 DETAIL 3 RESTROOM PLAN. |
| | HDCP STALL NOT WIDE ENOUGH. SHOWS 6'0" |
| | AND IT SHOULD BE 7'0" PER FACBC-97, FIG. |
| | 30(E). |
| | 3) PAGE A2.2 DETAIL 7 RESTROOM ELEVATION |
| | URNAL TO COMPLY WITH FACBC-97 SECTIONS |
| | 4.22.5 & 4.18.2. 17" TO LIP ECT. |
| | 4) PAGE A2.2 DETAIL 4 RESTROOM ENTRANCE |
| | ELEVATION. 1 DRINKING FOUNTAIN SHALL |
| | COMPLY WITH FACBC-97 SECT. 4.15, AND 1 |
| | DRINKING FOUNTAIN SHALL COMPLY WITH |
| | FACBC-97 SECT. 4.1.3(10). |
| | 5) PAGE P2 SANITARY RISER DIAGRAM. URNAL |
| | NOT SHOWN ON RISER DIAGRAM. |
| | 6) PAGE P2 WATER RISER DIAGRAM AND PLUMB |
| | ING NOTES #13. AIR CHAMBERS TO COMPLY |
| | WITH SPC-94 SECT. 607.8.2 & 607.8.3. |
| | ACCESSABLE AND RECHARGABLE. IF WATER |
| | HAMMER ARRESTORS ARE USED, THEY SHALL |
| | COMPLY WITH MANUFACTURE INSTALLATION IN- |
| | STRUCTIONS AND WH-PDI 201 FOR SIZING AND |
| | LOCATION. THEY ARE NOT LOCATED AT TOP OF |
| | RISERS OR DROPS. |
| | 7) PAGE P2 WATER HEATER DETAIL. SHUT OFF |
| | VALVE SHALL BE LOCATED CLOSE TO HEATER. |
| | (ACCESSABLE). |
| | 8) SHOW LOCATION OF WATER HEATER. PAN |
| | DRAIN TO BE 1", AND RELIEF VALVE DIS- |
| | CHARGE SHALL BE FULL SIZED SEPARATLY TO |
| | THE OUTSIDE OF THE BUILDING AND SHALL |
| | TERMINATE 6" ABOVE GRADE. SPC-94 SECTS. |
| | 507.8.2 & 507.8.4 |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 569-8096 EXT. 8377 |