2001-09-24 00:00:00********************DENIED**************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 1.FIRE DAMPERS ARE REQUIRED FOR DUCTS
 THAT PENETRATE A WALL OR PARTITION
 WITH A FIRE RESISTANCE RATING OF 1
 HOUR OR MORE.
  
 2.FIRE DAMPERS ARE ALSO REQUIRED FOR
 DUCTS PENETRATING ONLY ONE FLOOR OF
 A BUILDING REQUIRING THE PROTECTION
 OF VERTICAL OPENINGS WHEN THE DUCT
 IS NOT PROTECTED BY A SHAFT
 ENCLOSURE.
  
 3.FIRE DAMPER LOCATIONS SHALL BE
 IDENTIFIED ON THE PLAN.
  
 4.FIRE DAMPERS SHALL COMPLY WITH THE
 REQUIREMENTS OF UL 555 AND SHALL
 BEAR THE LABEL OF AN APPROVED
 TESTING AGENCY.
  
 5.PLEASE PROVIDE A DETAIL OF FIRE
 DAMPER INSTALLATION.
  
 6.PLEASE IDENTIFY CONDENSATE ON PLAN.
 AS PER AMENDED 1994 SPC 804.3, UNITS
 LARGER THAN 3 TONS SHALL TERMINATE
 INTO STORM DRAIN OR AN APPROVED
 DRYWELL.
  
 NOTE:FAN SHUTDOWN BY DUCT SMOKE
 DETECTOR SHALL HAVE NOTIFICATION
 TO ALARM/STROBE IN NORMALLY
 OCCUPIED AREAS. NFPA 90A 4-4.4.3.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.