| 2001-09-24 00:00:00 | ********************DENIED************** |
| | |
| | |
| | PLEASE PROVIDE THE FOLLOWING INFORMATION |
| | FOR REVIEW: |
| | |
| | 1.FIRE DAMPERS ARE REQUIRED FOR DUCTS |
| | THAT PENETRATE A WALL OR PARTITION |
| | WITH A FIRE RESISTANCE RATING OF 1 |
| | HOUR OR MORE. |
| | |
| | 2.FIRE DAMPERS ARE ALSO REQUIRED FOR |
| | DUCTS PENETRATING ONLY ONE FLOOR OF |
| | A BUILDING REQUIRING THE PROTECTION |
| | OF VERTICAL OPENINGS WHEN THE DUCT |
| | IS NOT PROTECTED BY A SHAFT |
| | ENCLOSURE. |
| | |
| | 3.FIRE DAMPER LOCATIONS SHALL BE |
| | IDENTIFIED ON THE PLAN. |
| | |
| | 4.FIRE DAMPERS SHALL COMPLY WITH THE |
| | REQUIREMENTS OF UL 555 AND SHALL |
| | BEAR THE LABEL OF AN APPROVED |
| | TESTING AGENCY. |
| | |
| | 5.PLEASE PROVIDE A DETAIL OF FIRE |
| | DAMPER INSTALLATION. |
| | |
| | 6.PLEASE IDENTIFY CONDENSATE ON PLAN. |
| | AS PER AMENDED 1994 SPC 804.3, UNITS |
| | LARGER THAN 3 TONS SHALL TERMINATE |
| | INTO STORM DRAIN OR AN APPROVED |
| | DRYWELL. |
| | |
| | NOTE:FAN SHUTDOWN BY DUCT SMOKE |
| | DETECTOR SHALL HAVE NOTIFICATION |
| | TO ALARM/STROBE IN NORMALLY |
| | OCCUPIED AREAS. NFPA 90A 4-4.4.3. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT 659-8096 EXT. |
| | 8388. |