| Plan Review Notes For Permit 01090052 |
| Permit Number |
01090052 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-09-05 00:00:00 | 1) PLEASE EXPLAIN HOW STOREFRONT DOORS | | | WILL MEET THE REQUIREMENTS FOR AT | | | LEAST 20 MINUTE FIRE RATINGS. | | | 2) STAIRS PROVIDING EXITING SHALL BE | | | ENCLOSED BY AT LEAST A ONE HOUR | | | FIRE SEPARATION. | | | 3) NO INTERIOR FINISH CLASSIFICATION | | | INFORMATION PROVIDED FOR WALLS AND | | | CEILINGS. | | | 4) EXITS FOR PROPOSED TENANT SPACE #1 | | | ARE NOT PROPERLY SEPARATED FROM ONE | | | ANOTHER BY DISTANCE AS REQUIRED BY | | | FIRE CODE REQUIREMENTS. | | | 5) WILL THE SECOND FLOOR HAVE A SINGLE | | | OR MULTIPLE TENANTS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|