Plan Review Notes
Plan Review Notes For Permit 01090052
Permit Number 01090052
Review Stop E
Sequence Number 1
Notes
Date Text
2001-09-18 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE CLARIFY SERVICE ENTRANCE
 CONDUCTORS? RISER SHOWS OH SERV AND
 SERVICE BEING INSIDE? SERVICE IS SHOWN
 ON SECOND FLOOR IN ROOM.? PLEASE CALRIFY
 PLEASE ALSO CLARIFY 2HR MEANS OF
 SEPARATION REQ`D FOR ADDITIONAL SERVICE
 UNDER 230-2. PIPE SHOWN GOING THROUGH
 EXISTING SEPARATE BLDG. 230-3.
  
 2)NOTE: PLEASE NOTE THAT ELECTRICAL ROOM
 WOULD REQ` 2HR SEPARATION FROM EXISTING
 SPACE FOR NEW SERVICE BEING ADDED.
 BLDG CODE AND FIRE CODE
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372