2001-09-24 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01090052
 314 CLEMATIS ST
 CONT : ITASCA CON
 (561) 241-4999
  
 TYPE V PROTECTED/SPRINKLERED
  
 COMMENT ON TENANT BUILDOUT!!! FUTURE
 TENANT BUILDOUT SPACE 210 IF SPACE IS
 SUBDIVIDED INTO SMALLER TENANT SPACES
 THERE MAYBE A PROBLEM, SBC 1020.1 SINGLE
 EXIT REQUIREMENTS, 75' MAXIMUM TRAVEL
 DISTANCE TO A SINGLE EXIT.
  
 1)- SHEET A2.1 DOORS 202,203,205,207&
 211 REQUIRE A RATING, NOT GIVEN?
 2)- DOOR 203 ELEVATOR MACHINE ROOM
 RATING?
 3)- STAIRWELL (201) REQUIRES A 1 HR EN-
 CLOSURE, IT IS A REQUIRED EXIT. BY DEFIN
 ITION, EXIT: THAT PORTION OF A MEANS OF
 EGRESS WHICH IS SEPERATED FROM ALL OTHER
 SPACES OF A BUILDING OR STRUCTURE BY
 CONSTRUCTION AND OPENING PROTECTIVES, AS
 REQUIRED FOR EXITS, TO PROVIDE A PROTECT
 ED WAY OF TRAVEL TO THE EXIT DISCHARGE.
 SBC 3003.1.4. ELEVATORS SHALL NOT BE IN
 A COMMON ENCLOSING SHAFT, AND THE PATH
 OF TRAVEL FROM ONE FLIGHT OF STAIRS TO
 THE NEXT SHALL NOT PASS DIRECTLY IN
 FRONT OF THE ELEVATOR DOORS.
 SEE 3003.1.5 ELEVATOR LOBBY EXCEPTION!
 4)-SHEET A2.1 WALL "A", A6.0 WALL SCHEDU
 LE INDICATES TEST UL: U-465 1 HR RATING
 S-2 INDICATES 18 GAUGE "FLEXIBLE" TOP &
 BOTTOM TRACK, DOES THE "FLEXIBLE TRACK"
 HAVE A UL RATING?
 5)- A2.2 DETAIL 3 RESTROOMS SEE ATTACHED
 DRAWINGS FOR NOTICE OF CHANGE TO THE
 FL ACCESSIBILITY CODE FOR HANDICAPPED
 RESTROOMS FIGURE 30(E).
 6)- SBC 1204.2 RESTROOMS FOR PUBLIC USE.
 THE WALLS & FLOORS OF ALL RESTROOMS
 (PUBLIC) SHALL BE LINED WITH NONABSORB-
 ANT MATERIALS TO A HEIGTH OF 4 FT ABOVE
 THE FLOOR.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096X 8412