| 2001-09-24 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 01090052 |
| | 314 CLEMATIS ST |
| | CONT : ITASCA CON |
| | (561) 241-4999 |
| | |
| | TYPE V PROTECTED/SPRINKLERED |
| | |
| | COMMENT ON TENANT BUILDOUT!!! FUTURE |
| | TENANT BUILDOUT SPACE 210 IF SPACE IS |
| | SUBDIVIDED INTO SMALLER TENANT SPACES |
| | THERE MAYBE A PROBLEM, SBC 1020.1 SINGLE |
| | EXIT REQUIREMENTS, 75' MAXIMUM TRAVEL |
| | DISTANCE TO A SINGLE EXIT. |
| | |
| | 1)- SHEET A2.1 DOORS 202,203,205,207& |
| | 211 REQUIRE A RATING, NOT GIVEN? |
| | 2)- DOOR 203 ELEVATOR MACHINE ROOM |
| | RATING? |
| | 3)- STAIRWELL (201) REQUIRES A 1 HR EN- |
| | CLOSURE, IT IS A REQUIRED EXIT. BY DEFIN |
| | ITION, EXIT: THAT PORTION OF A MEANS OF |
| | EGRESS WHICH IS SEPERATED FROM ALL OTHER |
| | SPACES OF A BUILDING OR STRUCTURE BY |
| | CONSTRUCTION AND OPENING PROTECTIVES, AS |
| | REQUIRED FOR EXITS, TO PROVIDE A PROTECT |
| | ED WAY OF TRAVEL TO THE EXIT DISCHARGE. |
| | SBC 3003.1.4. ELEVATORS SHALL NOT BE IN |
| | A COMMON ENCLOSING SHAFT, AND THE PATH |
| | OF TRAVEL FROM ONE FLIGHT OF STAIRS TO |
| | THE NEXT SHALL NOT PASS DIRECTLY IN |
| | FRONT OF THE ELEVATOR DOORS. |
| | SEE 3003.1.5 ELEVATOR LOBBY EXCEPTION! |
| | 4)-SHEET A2.1 WALL "A", A6.0 WALL SCHEDU |
| | LE INDICATES TEST UL: U-465 1 HR RATING |
| | S-2 INDICATES 18 GAUGE "FLEXIBLE" TOP & |
| | BOTTOM TRACK, DOES THE "FLEXIBLE TRACK" |
| | HAVE A UL RATING? |
| | 5)- A2.2 DETAIL 3 RESTROOMS SEE ATTACHED |
| | DRAWINGS FOR NOTICE OF CHANGE TO THE |
| | FL ACCESSIBILITY CODE FOR HANDICAPPED |
| | RESTROOMS FIGURE 30(E). |
| | 6)- SBC 1204.2 RESTROOMS FOR PUBLIC USE. |
| | THE WALLS & FLOORS OF ALL RESTROOMS |
| | (PUBLIC) SHALL BE LINED WITH NONABSORB- |
| | ANT MATERIALS TO A HEIGTH OF 4 FT ABOVE |
| | THE FLOOR. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |