2001-10-22 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01090049
 1555 PALM BEACH LAKES # 9TH FL
 ANDERSON MOORE CONSTRUCTION
 TEL : 626-4411
 FAX : 626-4411
 CELL: 662-1819
  
 SBC= 1997 STANDARD BUILDING CODE
  
 1)-SBC 412.6.1 REQUIRES THE ELEVATOR
 LOBBY TO BE SEPERATED FROM THE REMAINDER
 OF THE BUILDING WITH 1 HR RATED
 CONSTRUCTION.
 SBC 412.6.2 EXIT STAIRWAYS, CHUTES,
 JANITOR CLOSETS,SERVICE ROOMS- MECH.,
 GUEST ROOMS, ETC., SHALL NOT OPEN INTO
 THE ELEVATOR LOBBY.
  
 2)- SHEET A-1 DETAIL#2: PROVIDE A FIRE
 DESIGN NUMBER FOR THE PARTITION DEPICTED
  
 3)- FL ACCES CODE 4.13.6 MANEUVERING
 CLEARENCES AT DOORS, 23 & 34 REQUIRE
 12" ON THE PUSH SIDE OF THE DOOR.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096X8412