| Plan Review Notes For Permit 01090049 |
| Permit Number |
01090049 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-10-22 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01090049 | | | 1555 PALM BEACH LAKES # 9TH FL | | | ANDERSON MOORE CONSTRUCTION | | | TEL : 626-4411 | | | FAX : 626-4411 | | | CELL: 662-1819 | | | | | | SBC= 1997 STANDARD BUILDING CODE | | | | | | 1)-SBC 412.6.1 REQUIRES THE ELEVATOR | | | LOBBY TO BE SEPERATED FROM THE REMAINDER | | | OF THE BUILDING WITH 1 HR RATED | | | CONSTRUCTION. | | | SBC 412.6.2 EXIT STAIRWAYS, CHUTES, | | | JANITOR CLOSETS,SERVICE ROOMS- MECH., | | | GUEST ROOMS, ETC., SHALL NOT OPEN INTO | | | THE ELEVATOR LOBBY. | | | | | | 2)- SHEET A-1 DETAIL#2: PROVIDE A FIRE | | | DESIGN NUMBER FOR THE PARTITION DEPICTED | | | | | | 3)- FL ACCES CODE 4.13.6 MANEUVERING | | | CLEARENCES AT DOORS, 23 & 34 REQUIRE | | | 12" ON THE PUSH SIDE OF THE DOOR. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561)659-8096X8412 |
|