Plan Review Notes
Plan Review Notes For Permit 01090049
Permit Number 01090049
Review Stop P
Sequence Number 1
Notes
Date Text
2001-09-12 00:00:00DENIED
 REFERENCES SPC-94 - FACBC-97
  
 1) PAGE A-3 HDCP RESTROOM, LAV TO COMPLY
 WITH FACBC-97 SECT. 4.19.2.
  
 2) PAGE A-3 WATER RISER DIAGRAM. AIR
 CHAMBERS TO COMPLY WITH SPC-94 SECT.
 607.8.3 ACCESSABLE AND RECHARGABLE. IF
 WATER HAMMER ARRESTORS ARE USED THEY
 SHALL COMPLY WITH MANUFACTURE'S INSTALL-
 ATION INSTRUCTIONS AND WH-PDI 201 FOR
 SIZE AND LOCATION. (NOT AT TOP OF DROP)
  
 3) PAGE A-3 WATER RISER DIAGRAM. EACH
 WATER SUPPLY BRANCH LINE SHALL HAVE A
 SHUTOFF VALVE INSTALLED. SPC-94 SEC.
 610.4.2
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377