| Plan Review Notes For Permit 01090049 |
| Permit Number |
01090049 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-09-12 00:00:00 | DENIED | | | REFERENCES SPC-94 - FACBC-97 | | | | | | 1) PAGE A-3 HDCP RESTROOM, LAV TO COMPLY | | | WITH FACBC-97 SECT. 4.19.2. | | | | | | 2) PAGE A-3 WATER RISER DIAGRAM. AIR | | | CHAMBERS TO COMPLY WITH SPC-94 SECT. | | | 607.8.3 ACCESSABLE AND RECHARGABLE. IF | | | WATER HAMMER ARRESTORS ARE USED THEY | | | SHALL COMPLY WITH MANUFACTURE'S INSTALL- | | | ATION INSTRUCTIONS AND WH-PDI 201 FOR | | | SIZE AND LOCATION. (NOT AT TOP OF DROP) | | | | | | 3) PAGE A-3 WATER RISER DIAGRAM. EACH | | | WATER SUPPLY BRANCH LINE SHALL HAVE A | | | SHUTOFF VALVE INSTALLED. SPC-94 SEC. | | | 610.4.2 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|