Plan Review Notes
Plan Review Notes For Permit 01090049
Permit Number 01090049
Review Stop B
Sequence Number 1
Notes
Date Text
2001-09-18 00:00:00THE COMMON PATH OF TRAVEL FROM THE
 VICINITY OF OFFICE #132 EXCEEDS THE 75'
 ALLOWED BY SBC 1004.1.3.PLEASE REVISE
 AS NECESSARY.
  
 SBC 412.6.1 REQUIRES ELEVATOR LOBBIES TO
 BE SEPARATED FROM THE REMAINDER OF THE
 BUILDING WITH 1 HOUR FIRE RATED
 CONSTRUVCTION.SEE ALSO 412.6.2.
  
 THE EXIT DOORS SERVING THE NORTH SIDE
 OFFICE SPACE DO NOT MEET THE 1/2
 DIAGONAL DISTANCE SEPARATION
 REQUIREMENTS OF SBC 1004.1.4.PLEASE
 REVISE AS NECESSARY.
  
 PROVIDE A FIRE DESIGN NUMBER FOR THE
 PARTITION SHOWN IN SECTION 2/A1.SEE
 SBC 701.5.