| 2001-09-18 00:00:00 | THE COMMON PATH OF TRAVEL FROM THE | | | VICINITY OF OFFICE #132 EXCEEDS THE 75' | | | ALLOWED BY SBC 1004.1.3.PLEASE REVISE | | | AS NECESSARY. | | | | | | SBC 412.6.1 REQUIRES ELEVATOR LOBBIES TO | | | BE SEPARATED FROM THE REMAINDER OF THE | | | BUILDING WITH 1 HOUR FIRE RATED | | | CONSTRUVCTION.SEE ALSO 412.6.2. | | | | | | THE EXIT DOORS SERVING THE NORTH SIDE | | | OFFICE SPACE DO NOT MEET THE 1/2 | | | DIAGONAL DISTANCE SEPARATION | | | REQUIREMENTS OF SBC 1004.1.4.PLEASE | | | REVISE AS NECESSARY. | | | | | | PROVIDE A FIRE DESIGN NUMBER FOR THE | | | PARTITION SHOWN IN SECTION 2/A1.SEE | | | SBC 701.5. |
|