| 2001-10-31 00:00:00 | 1) NEW METAL FIRE-STAIR HAS CODE | | | PROBLEMS. THE MAXIMUM HEIGHT OF | | | RISERS SHALL NOT EXCEED 7 INCHES. THE | | | MINIMUM TREAD DEPTH SHALL BE AT LEAST | | | 11". | | | 2) THE TRANSITION AREA WHERE THE | | | CHANGE OF ELEVATION OCCURS DOES NOT | | | MEET CODE. TREADS AND RISERS DO NOT | | | MEET CODE REQUIREMENTS. | | | 3) THE SMOKE DETECTOR MUST BE LOCATED | | | IN THE RESIDENTIAL PORTION OF THE | | | UNIT AND WHEN SOUNDING SHALL BE HEARD | | | WITHIN THE SLEEPING AREA. | | | 4) SECURITY GATE APPEARS TO SWING OVER | | | PROPERTY LINE SHOWN ON THE DRAWING. | | | | | | IT APPEARS THAT THE REST OF THE | | | DRAWING WOULD BE ACCEPTABLE TO THIS | | | OFFICE AFTER THE CODE VIOLATIONS ARE | | | CORRECTED. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|