| Plan Review Notes For Permit 01081573 |
| Permit Number |
01081573 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-09-25 00:00:00 | THE 4" SLAB CONSTRUCTED UNDER PERMIT | | | 00110838 IS INADEQUATE FOR A FOUNDATION. | | | SEE SBC 1804.1.3 AND REVISE AS NECESSARY | | | | | | PROVIDE A MORE DETAILED PLAN FOR THE | | | CONNECTION OF THE TRUSSES TO THE | | | BUILDING, INCLUDE AN ANALYSIS OF THE | | | LOADING THAT WILL BE ASSUMED BY THE | | | TAPCONS. | | | | | | SPECIFY THE TRUSS ANCHORS TO BE USED OR | | | THE LOADS TO BE RESISTED RE: SECTION A. | | | | | | SPECIFY THE WALL THICKNESS AND WELD | | | DETAIL FOR THE 3 X 3 STEEL COLUMNS. | | | | | | SHOW THE CONNECTION DETAILS FOR THE | | | PRECAST COLUMN COVERS. | | | | | | SHOW THE ROOF VENTILATION FOR THE ATTIC | | | SPACE REQUIRED BY SBC 2309.7. | | | | | | DETAIL "B"HOW IS THIS CONNECTED?IS | | | THE EXISTING HOUSE BLOCK, TILE OR WOOD | | | FRAME? | | | | | | PROVIDE TEST REPORTS OR NOTICE OF ACCEPT | | | ANCE FOR THE ROOF COVERING. |
|