Plan Review Notes
Plan Review Notes For Permit 01081573
Permit Number 01081573
Review Stop B
Sequence Number 1
Notes
Date Text
2001-09-25 00:00:00THE 4" SLAB CONSTRUCTED UNDER PERMIT
 00110838 IS INADEQUATE FOR A FOUNDATION.
 SEE SBC 1804.1.3 AND REVISE AS NECESSARY
  
 PROVIDE A MORE DETAILED PLAN FOR THE
 CONNECTION OF THE TRUSSES TO THE
 BUILDING, INCLUDE AN ANALYSIS OF THE
 LOADING THAT WILL BE ASSUMED BY THE
 TAPCONS.
  
 SPECIFY THE TRUSS ANCHORS TO BE USED OR
 THE LOADS TO BE RESISTED RE: SECTION A.
  
 SPECIFY THE WALL THICKNESS AND WELD
 DETAIL FOR THE 3 X 3 STEEL COLUMNS.
  
 SHOW THE CONNECTION DETAILS FOR THE
 PRECAST COLUMN COVERS.
  
 SHOW THE ROOF VENTILATION FOR THE ATTIC
 SPACE REQUIRED BY SBC 2309.7.
  
 DETAIL "B"HOW IS THIS CONNECTED?IS
 THE EXISTING HOUSE BLOCK, TILE OR WOOD
 FRAME?
  
 PROVIDE TEST REPORTS OR NOTICE OF ACCEPT
 ANCE FOR THE ROOF COVERING.