| Plan Review Notes For Permit 01081558 |
| Permit Number |
01081558 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-09-06 00:00:00 | 1) FIRE RESCUE ACCESS TO BE AT LEAST | | | 20 FEET IN CLEAR WIDTH. | | | 2) THE KNOX-BOX KEY SWITCH SHOWN ON | | | THE DRAWINGS IS TO BE TESTED WITH FIRE | | | RESCUE PERSONNEL AFTER INSTALLATION. | | | 3) COVERED ENTRY FROM GUARDHOUSE IS | | | NOT APPROVED AND THEREFORE CANNOT | | | BE CONSTRUCTED AS MINIMUM HEIGHT | | | REQUIREMENTS APPLY FOR FIRE RESCUE | | | ACCESS. | | | | | | APPROVED PROVISO: | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|