2001-09-28 00:00:00*************BUILDING UNSAT*************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) THE BUILDING OFFICIAL WILL ALLOW A
 PRIVACY WALL WITH AN ACCESS PANEL FOR
 EGRESS. HOWEVER, THE 30"X 30" ACCESS
 PANEL OPENS INTO THE PRIVATE PROPERTY OF
 THE ADJACENT LOT. PLEASE PROVIDE
 DOCUMENTATION THAT THERE IS AN EGRESS
 EASEMENT OR OTHER THAT WILL PREVENT THE
 ACCESS DOOR AND EGRESS FROM BEING
 BLOCKED BY SHRUBBERY, FENCE, POOL OR
 OTHER BARRIER.
  
 3) THE ACCESS PANEL ON SHEET A-1.0 IS
 SHOWN AS 30"X 30" AND ON SHEET A-2.0
 THE HEIGHT IS GIVEN AS 3'-0". PLEASE
 CORRECT.
  
 4) THE MASONRY OPENING FOR THE GLASS
 BLOCK IN THE KITCHEN IS INCORRECTLY
 LISTED AS 85 SQ FT. PLEASE CORRECT.
  
 5) BUCK FASTENING DETAILS ON SHEET A-4.0
 AND NAILING SCHEDULE FOR BUCKS ON SHEET
 S2 CONTAIN CONFLICTING INFORMATION.
 PLEASE CORRECT.
  
 6) THE SOIL REPORT CALLS FOR FOUNDATIONS
 TO BEAR 14 INCHES BELOW GRADE. SECTION C
 ON SHEET A-3.0 SHOWS ONLY 12 IN. BELOW
 FINAL GRADE. PLEASE CORRECT.
 NOTE: THE CITY AMENDMENTS TO THE 97 SBC
 REQUIRE THAT THE BUILDING FLOOR
 ELEVATION AT THE PERIMETER OF A MONO-
 LITHIC FOUNDATION AT HABITABLE AREAS
 SHALL BE A MINIMUM OF 4 INCHES ABOVE
 FINISH GRADE.
  
 7)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR GLASS BLOCK. THE ONES THAT
 WERE SUBMITTED HAD EXPIRED PRIOR TO
 APPLYING FOR PERMIT.
  
 8) PROVIDE THE PRODUCT APPROVALS FOR THE
 STORM PANELS. THESE ARE REQUIRED IN
 ADDITION TO THE KEY PLAN, INSTALLATION
 SCHEDULE AND APPROVED DRAWINGS WHICH
 WERE SUBMITTED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202
  
  
 TRUSSES
 UNSAT
  
 1) THE TRUSS LAYOUT AND DRAWINGS MUST BE
 REVIEWED AND APPROVED BY THE DESIGNER OF
 RECORD OF THE STRUCTURE. IF THEY ARE
 ACCEPTABLE,THE DESIGN PROFESSIONAL IS TO
 STATE THIS ON THE TRUSS LAYOUT AND SIGN
 IT.
  
 2) TRUSS T2 EXCEEDS THE ANCHOR CAPACITY
 AT BOTH ENDS.
  
 3) THE PLANS DO NOT INDICATE THE TRUSS
 ANCHOR TO BE USED FOR TRUSS T1 AT THE
 LEDGER.
  
 4) TRUSS GT3 EXCEEDS ANCHOR CAPACITY AT
 BOTH ENDS.
  
 5) TRUSS GT11 EXCEEDS THE ANCHOR
 CAPACITY ON ONE END.
  
 6) THE TURRET FRAMING PLAN ON S1 LISTS
 A TA-6 TRUSS ANCHOR. THIS MARK IS NOT
 LISTED IN THE ANCHOR SCHEDULE ON S2.
  
 7) THE TRUSS DRAWINGS INDICATE A WALL
 HEIGHT OF 26 FT. THE HIGHEST WALL IN THE
 STRUCTURE IS +15' AT THE TURRET.