Plan Review Notes For Permit 01081536
Permit Number 01081536
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-09-25 00:00:001) PLEASE BE ADVISED THAT THE WOOD SHED
 WITH METAL SIDING IS TOO CLOSE TO THE
 BULK OXYGEN TANK. THE BULK OXYGEN TANK
 MUST BE SEPARATED BY AT LEAST 50 FEET
 FROM WOOD FRAME BUILDINGS. PLEASE SEE
 NFPA 50, SECTION 2.2.1.
 2) NO PARKING OR PUBLIC SIDEWALKS ARE
 PERMITTED WITHIN 10 FEET OF BULK
 OXYGEN TANK. PLEASE SEE NFPA 50,SECTION
 2.2.12.
 3) BULK OXYGEN TANKS MUST BE AT LEAST
 50 FEET FROM ANY NON-AMBULATORY AREAS.
 PLEASE SEE NFPA 50,SECTION 2.2.11
 4) SAFETY RELEASE DEVICES ARE REQUIRED.
 PLEASE SEE NFPA 50,SECTION 3-3.
 5) SIGNAGE REQUIRED "OXYGEN,NO SMOKING,
 OR OPEN FLAMES". PLEASE SEE NFPA 50,
 SECTION 3.5.8.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910