| Plan Review Notes For Permit 01081524 |
| Permit Number |
01081524 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-10-01 00:00:00 | **************** UNSAT ************ | | | | | | 1)NOTE: PLEASE NOTE THAT RESPONSE TO | | | FIRST COMMENT IN LETTER, PLEASE NOTE | | | THAT ART: 220-12B DOES NOT MENTION ANY- | | | -THING ABOUT TRACK LIGHTING AT STORE | | | FRONTS. 220-12A PERTAINS TO LOADS FOR | | | RECEPTS AT STOREFRONTS ONLY. | | | TRACK LIGHTING LOADS ARE FOR ANYWHERE | | | IN THE STORE. | | | | | | 2)NOTE: PLEASE NOTE THAT AMENDED PLANS | | | ARE NOT SIGNED,DATED OR SEALED BY THE | | | ENGINEER OF RECORD. PER 471.025 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|