Plan Review Notes
Plan Review Notes For Permit 01081524
Permit Number 01081524
Review Stop E
Sequence Number 1
Notes
Date Text
2001-09-10 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SHOW LOAD CALCUALTIONS
 FOR TRACK LIGHTING PER 220-12B
  
 2)NOTE: PLEASE NOTE THAT PLANS SHOW
 COLOR CODING FOR 277V/480V TO BE ORANGE
 FOR B PHASE, PLEASE NOTE THAT COLOR
 PER LOCAL AMENDMENT FOR 277/480 IS TO BE
 PURPLE. ART:215 LOCAL
  
 3)NOTE: PLEASE NOTE OUTLET SPACING TO
 MEET LOCAL CODE FOR STORAGE AREA AND
 SALES AREA, EVERY 20' OF WALL SPACE.
  
 4)NOTE: PLEASE NOTE THAT PLAN COVER PAGE
 CALL FOR 1996 NEC. PLEASE NOTE THAT
 WE ARE UNDER THE "99" NEC. PLEASE CHANGE
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372