| Plan Review Notes For Permit 01081498 |
| Permit Number |
01081498 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-09-10 00:00:00 | DENIED | | | | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) PAGE 1, SINK TO COMPLY WITH FACBC-97 | | | SECT. 2.24. PLEASE SUBMIT DETAIL TO SHOW | | | COMPLIANCE FOR THIS SINK. | | | | | | 2) PAGE 8. AIR CHAMBER TO COMPLY WITH | | | SPC-94 SECTIONS 607.8.2 & 607.8.3, ACC- | | | ESSABLE AND RECHARGABLE. IF WATER HAMMER | | | ARRESTOR IS USED IT SHALL COMPLY WITH | | | MANUFACTURE'S INSTALLATION INSTRUCTIONS | | | AND WH-PDI 201. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|