| 2001-09-28 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT #01081489 |
| | 323 MANGO PROMENADE |
| | O/B BUSSEY, MARVIN D. |
| | SBC= 1997 STANDARD BUILDING CODE |
| | 1)- ROOFING: SBC 1503.3.2 ROOF ASSEM- |
| | BLIES SHALL BE TESTED FOR 110 MPH WIND |
| | ZONE. THE CITY ACCEPTS ROOFING REPORTS |
| | FROM SBCCI OR DADE COUNTY PRODUCT APPROV |
| | ALS. |
| | |
| | 2)- THE RECONFIGURATION OF THE FRONT |
| | WALL UNDER THE FRONT PORCH, SHOW WALL |
| | SECTION, DETAILS OF STRAPING TOP / BOT- |
| | TOM PLATES HEADER SIZE AND JACK STUDS. |
| | |
| | 3)- SSBC 104.2.2. DISCREPANCY, MORE |
| | INFORMATION REQUIRED, PAGE 2 INDICATE RE |
| | PAIR OF 12" FLOOR JOIST BUT DEPICTED ARE |
| | FLOOR TRUSSES, WHICH ARE THEY & WHAT |
| | TYPE OF REPAIR IS REQUIRED. |
| | |
| | 4)- SBC 1606.4.1/ 1707.4.1 WINDOWS: |
| | A SEPERATE PERMIT WAS PULLED TO REPLACE |
| | OVER 50 % OF THE GLAZED OPENINGS IN THE |
| | HOUSE. BY CODE SEE ATTACHMENT ARTICLE |
| | #(4) WHEN 50% OF OPENINGS ARE REPLACED |
| | AND THE WINDOWS DO NOT HAVE LARGE MISSLE |
| | IMPACT THEY WILL REQUIRE STORM SHUTTERS. |
| | SBCCI REPORTS OR DADE COUNTY PRODUCT APP |
| | ROVAL (2) COPIES. ATTACHED IS A COPY OF |
| | A FASTENING SCHEDULE. |
| | |
| | 5)- DEMONSTRATE CODE COMPLIANCE: DOES |
| | THE ROOF FRAMING SYSTEM HAVE CONTINIOUS |
| | STRAPING FROM ROOF FRAMING MEMBERS TO |
| | THE WALL MEMBERS, HEADERS TO VERTICAL |
| | FRAMING MEMBERS. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |