| Plan Review Notes For Permit 01081470 |
| Permit Number |
01081470 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-31 00:00:00 | CHECKLIST: | | | 1-PROVIDE COMPLETE CALCULATIONS SHOWING | | | ALL DESIGN LOADS AND DESIGN CRITERIA | | | ASSUMPTIONS. | | | -BE SPECIFIC: USE SBC 1997 FOR LOADS | | | CONSIDERATIONS. | | | 2-THERE IS NO INFORMATION REGARDING THE | | | FOOTINGS FOR THE NEW COLUMNS. | | | -WHAT ARE THE DESIGN ASSUMPTIONS? SIZE | | | OF FOOTINGS? OFF-SET LOADING? | | | -ARE EXISTING FOOTINGS ADEQUATE TO | | | CARRY THE ADDITIONAL LOAD? SPECIFY | | | SIZES. | | | 3-HOW MANY STORIES ARE CONSIDERED IN | | | THIS BUILDING? |
|