| Plan Review Notes For Permit 01081416 |
| Permit Number |
01081416 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2003-02-03 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SHT 11 SANITARY RISER DIAGRAM DOES | | | NOT MEET CODE OR REFLECT FLOOR PLAN. | | | A) BATH #2 FROM THE SECOND FLOOR SHALL | | | NOT TIE INTO DRAIN BETWEEN THE W/C AND | | | THE LAV (VENT FOR POWDER ROOM) IN THE | | | POWDER ROOM. | | | B) BATH #2 SHOWS A SHOWER ON THE RISER | | | DIAGRAM, BUT IS REMOVED ON FLOOR PLAN. | | | PLEASE CLAIRFY. | | | C) BAR SINK SHALL NOT DRAIN INTO THE | | | WET VENT FOR BATHROOM #4. SINK SHALL TIE | | | IN DOWN STREAM OF THE BATHROOM GROUP. | | | SECTION 909.1. | | | | | | PLEASE MAKE CHANGES AND RESUBMIT. | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|