Plan Review Notes
Plan Review Notes For Permit 01081416
Permit Number 01081416
Review Stop P
Sequence Number 4
Notes
Date Text
2003-02-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT 11 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE OR REFLECT FLOOR PLAN.
 A) BATH #2 FROM THE SECOND FLOOR SHALL
 NOT TIE INTO DRAIN BETWEEN THE W/C AND
 THE LAV (VENT FOR POWDER ROOM) IN THE
 POWDER ROOM.
 B) BATH #2 SHOWS A SHOWER ON THE RISER
 DIAGRAM, BUT IS REMOVED ON FLOOR PLAN.
 PLEASE CLAIRFY.
 C) BAR SINK SHALL NOT DRAIN INTO THE
 WET VENT FOR BATHROOM #4. SINK SHALL TIE
 IN DOWN STREAM OF THE BATHROOM GROUP.
 SECTION 909.1.
  
 PLEASE MAKE CHANGES AND RESUBMIT.
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377