| Plan Review Notes For Permit 01081416 |
| Permit Number |
01081416 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-04-25 00:00:00 | ***************REVISION NEEDED ********* | | | | | | 1)NOTE: PLEASE NOTE THAT THERE ARE | | | EQUIPMENT GROUNDING CONDUCTORS SHOWN | | | BETWEEN METER AND FIRST MEANS OF DISC. | | | PLEASE NOTE THAT THIS IS PARALLELING THE | | | NEUTRAL WHICH IS NOT PERMITTED. | | | | | | 2)NOTE: PLEASE NOTE MISSING EQUIPMENT | | | GROUND BETWEEN MAINS AND DISC`S 250-122. | | | | | | | | | 3)NOTE: PLEASE NOTE MISSING SD`S UP AND | | | DOWN STAIRS TO BE IN CLOSE PROXIMITY AND | | | LEADING TO THE FLOOR ABOVE. 2-2.1.1.1, | | | 2-5.2.1.4 | | | | | | 4)NOTE: PLEASE NOTE THAT THE SERVICE | | | ENTRANCE CONDUCTOR ARE SHOWN AS ONE | | | SIZE ON SHEET 10 AND ANOTHER ON SHEET | | | 11? PLEASE CORRELATE PLANS FOR THE | | | CONDUCTOR SIZES. | | | | | | 5)NOTE: PLEASE NOTE MISSING OUTLET | | | LOWER LEVEL.210-52 | | | | | | PLEASE REVISE THE ABOVE AND SUBMIT FOR | | | REVIEW BEFORE FINAL ELEC INSPECTION IS | | | CALLED IN. IF THERE ARE NAY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|