2002-04-25 00:00:00***************REVISION NEEDED *********
  
 1)NOTE: PLEASE NOTE THAT THERE ARE
 EQUIPMENT GROUNDING CONDUCTORS SHOWN
 BETWEEN METER AND FIRST MEANS OF DISC.
 PLEASE NOTE THAT THIS IS PARALLELING THE
 NEUTRAL WHICH IS NOT PERMITTED.
  
 2)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUND BETWEEN MAINS AND DISC`S 250-122.
  
  
 3)NOTE: PLEASE NOTE MISSING SD`S UP AND
 DOWN STAIRS TO BE IN CLOSE PROXIMITY AND
 LEADING TO THE FLOOR ABOVE. 2-2.1.1.1,
 2-5.2.1.4
  
 4)NOTE: PLEASE NOTE THAT THE SERVICE
 ENTRANCE CONDUCTOR ARE SHOWN AS ONE
 SIZE ON SHEET 10 AND ANOTHER ON SHEET
 11? PLEASE CORRELATE PLANS FOR THE
 CONDUCTOR SIZES.
  
 5)NOTE: PLEASE NOTE MISSING OUTLET
 LOWER LEVEL.210-52
  
 PLEASE REVISE THE ABOVE AND SUBMIT FOR
 REVIEW BEFORE FINAL ELEC INSPECTION IS
 CALLED IN. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.
  