| 2002-02-26 00:00:00 | ***************UNSAT!******************* |
| | PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION AND RESUBMIT FOR REVIEW: |
| | |
| | 1) AN A.I.C. RATING TO THE FIRST MEANS |
| | OF DISCONNECT AND INDICATE THE RATING |
| | OF OCP FOR SAME. |
| | |
| | 2) INDICATE THE LOCATION OF THE SERVICE |
| | ON THE PLAN. |
| | |
| | 3) INDICATE PANEL LOCATIONS ON PLAN,ALSO |
| | SIZE AND TYPE OF RACEWAYS AND |
| | CONDUCTORS FEEDING SAME.(CONDUITS |
| | LEAVING PANELS "A" & "B" ARE NOTED AS |
| | GOING "TO HOUSE SERVICE",PLEASE |
| | CLARIFY.) |
| | |
| | 4) THERE ARE NO BATH ROOM G.F.I'S ON |
| | PANEL SCHEDULES ( OR ADDED TO LOAD |
| | CALCULATIONS) AS PER 210-11(C)(3). |
| | |
| | 5) THE WATER HEATER CIRCULATING PUMP IS |
| | NOT SHOWN ON PANEL SCHEDULE. |
| | |
| | 6) WATER HEATER IS LISTED AT 1.5 |
| | KW.,PLEASE CONFIRM. |
| | |
| | 7) OVEN IS LISTED AT 1.5KW.PLEASE |
| | CONFIRM.A GAS COOKTOP IS SHOWN ON PLAN, |
| | AND A 8 KW. RANGE.PLEASE CLARIFY WHAT |
| | APPLIANCES ARE BEING INSTALLED AND THE |
| | CORRECT NAME PLATE RATING FOR SAME. |
| | |
| | 8) PANEL "B" LOAD CALCS SHOW 3 AHU'S AT |
| | 10KW'S EACH.AIR HANDLER CALCS SHOW A |
| | TOTAL OF 20KW'S FOR THESE THREE |
| | UNITS.PLEASE CORRECT. |
| | |
| | 9) ACCU'S #1,2,&3 ARE LISTED ON 40 AMP |
| | BREAKERS PROTECTING #10 WIRE.CLARIFY. |
| | |
| | 10) THE WATER HEATER LISTED ON PANEL"B" |
| | IS SHOWN ON A SINGLE POLE BREAKER,BUT |
| | LISTED ON CIRCUITS 10 & 12. |
| | |
| | 11) THE DRYER LISTED ON PANEL"A"IS SHOWN |
| | ON CIRCUIT #2.IT IS ALSO SHOWN AS 8KW. |
| | |
| | 12) KITCHEN COUNTER TOP RECEPTACLES PER |
| | 210-52(C)(1). |
| | |
| | 13) PLEASECHECK RECEPTACLE LOCATIONS |
| | TO COMPLY WITH 210-52(A)(2)(A).SEE |
| | PLANS. |
| | |
| | 14) PLEASE NOTE SMOKE DETECTOR |
| | LOCATIONS AND COMPLY WITH NFPA-72. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/ 659-8096 EXT.8392 |