Plan Review Notes
Plan Review Notes For Permit 01081416
Permit Number 01081416
Review Stop E
Sequence Number 1
Notes
Date Text
2002-02-26 00:00:00***************UNSAT!*******************
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND RESUBMIT FOR REVIEW:
  
 1) AN A.I.C. RATING TO THE FIRST MEANS
 OF DISCONNECT AND INDICATE THE RATING
 OF OCP FOR SAME.
  
 2) INDICATE THE LOCATION OF THE SERVICE
 ON THE PLAN.
  
 3) INDICATE PANEL LOCATIONS ON PLAN,ALSO
 SIZE AND TYPE OF RACEWAYS AND
 CONDUCTORS FEEDING SAME.(CONDUITS
 LEAVING PANELS "A" & "B" ARE NOTED AS
 GOING "TO HOUSE SERVICE",PLEASE
 CLARIFY.)
  
 4) THERE ARE NO BATH ROOM G.F.I'S ON
 PANEL SCHEDULES ( OR ADDED TO LOAD
 CALCULATIONS) AS PER 210-11(C)(3).
  
 5) THE WATER HEATER CIRCULATING PUMP IS
 NOT SHOWN ON PANEL SCHEDULE.
  
 6) WATER HEATER IS LISTED AT 1.5
 KW.,PLEASE CONFIRM.
  
 7) OVEN IS LISTED AT 1.5KW.PLEASE
 CONFIRM.A GAS COOKTOP IS SHOWN ON PLAN,
 AND A 8 KW. RANGE.PLEASE CLARIFY WHAT
 APPLIANCES ARE BEING INSTALLED AND THE
 CORRECT NAME PLATE RATING FOR SAME.
  
 8) PANEL "B" LOAD CALCS SHOW 3 AHU'S AT
 10KW'S EACH.AIR HANDLER CALCS SHOW A
 TOTAL OF 20KW'S FOR THESE THREE
 UNITS.PLEASE CORRECT.
  
 9) ACCU'S #1,2,&3 ARE LISTED ON 40 AMP
 BREAKERS PROTECTING #10 WIRE.CLARIFY.
  
 10) THE WATER HEATER LISTED ON PANEL"B"
 IS SHOWN ON A SINGLE POLE BREAKER,BUT
 LISTED ON CIRCUITS 10 & 12.
  
 11) THE DRYER LISTED ON PANEL"A"IS SHOWN
 ON CIRCUIT #2.IT IS ALSO SHOWN AS 8KW.
  
 12) KITCHEN COUNTER TOP RECEPTACLES PER
 210-52(C)(1).
  
 13) PLEASECHECK RECEPTACLE LOCATIONS
 TO COMPLY WITH 210-52(A)(2)(A).SEE
 PLANS.
  
 14) PLEASE NOTE SMOKE DETECTOR
 LOCATIONS AND COMPLY WITH NFPA-72.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/ 659-8096 EXT.8392