| Notes |
| Date |
Text |
| 2001-09-05 00:00:00 | 1) PLEASE SHOW DISTANCES OF PROPOSED | | | PROPANE TANK TO PROPERTY LINES, | | | EASEMENTS, OVERHEAD POWER LINES, ETC. | | | 2) PLEASE INDICATE METHODS USED TO | | | PROTECT THE PROPANE TANK FROM VANDALISM. | | | 3) PLEASE INDICATE WARNING LABELS, SIGNS | | | ETC. | | | 4) PLEASE INDICATE EXIT DOOR LOCATIONS | | | FROM WAREHOUSE TO THE PLANNED PROPANE | | | TANK. | | | 5) PLANS DO NOT INDICATE COMPLIANCE | | | WITH NFPA 58, THE STANDARD FOR THE | | | STORAGE AND HANDLING OF LP GAS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|