| Plan Review Notes For Permit 01081370 |
| Permit Number |
01081370 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-09-12 00:00:00 | *************** UNSAT **************** | | | | | | 1)NOTE: PLEASE PROVIDE A RISER DIAGRAM | | | SHOWING SERVICE. PLEASE SHOW GROUNDING | | | FOR DETACHED STRUCTURE. | | | | | | 2)NOTE: PLEASE SHOW PANEL LOCATION ON | | | PLANS. | | | | | | 3)NOTE: PLEASE SHOW CONDUCTORS FROM | | | HOUSE TO SHED. | | | | | | 4)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | SHOWING NEW LOADS BEING ADDED TO | | | EXISTING SERVICE. | | | | | | 5)NOTE:PLEASE NOTE THATS PLANS HAVE TO | | | BE SIGNED,DATED AND SEALED BY THE ARCH | | | OF RECORD PER 481.321. | | | | | | 6)NOTE:PLEASE CLARIFY THE MEANS OF DISC | | | AT DETACHED STRUCTURE PER 225-31 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS , | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|