Plan Review Notes
Plan Review Notes For Permit 01081370
Permit Number 01081370
Review Stop E
Sequence Number 1
Notes
Date Text
2001-09-12 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE PROVIDE A RISER DIAGRAM
 SHOWING SERVICE. PLEASE SHOW GROUNDING
 FOR DETACHED STRUCTURE.
  
 2)NOTE: PLEASE SHOW PANEL LOCATION ON
 PLANS.
  
 3)NOTE: PLEASE SHOW CONDUCTORS FROM
 HOUSE TO SHED.
  
 4)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 SHOWING NEW LOADS BEING ADDED TO
 EXISTING SERVICE.
  
 5)NOTE:PLEASE NOTE THATS PLANS HAVE TO
 BE SIGNED,DATED AND SEALED BY THE ARCH
 OF RECORD PER 481.321.
  
 6)NOTE:PLEASE CLARIFY THE MEANS OF DISC
 AT DETACHED STRUCTURE PER 225-31
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS ,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372