| 2001-08-27 00:00:00 | 1) NO INFORMATION PROVIDED ON THE CFM'S | | | EXPECTED FROM THE EXHAUST DUCT SYSTEM. | | | 2) NO DETAILS PROVIDED ON FILTER TYPES | | | PLANNED FOR THE FILTERING SYSTEM. | | | 3) HOW WILL THE SPRAY BOOTH BE GROUNDED. | | | 4) MORE DETAILS REQUIRED ON THE | | | WATER-WASH SYSTEM PLANNED FOR USE. | | | 5) NO DIMENSIONS SHOWN INDICATING A | | | THREE FOOT CLEARANCE AROUND SPRAY | | | BOOTH. | | | 6) THE DOUBLE 5/8" DRYWALL SHOWN ON | | | PLANS IS NOT SPECIFIC ENOUGH. IS THIS | | | DRYWALL FIRE RATED. | | | 7) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR THE INSTALLATION OF THE FIRE | | | SUPPRESSION SYSTEM PLANNED FOR USE. | | | 8) IS THE WATERWASH COLLECTION POINT | | | ON PRIVATE PROPERTY, EASEMENTS, OR | | | RAILROAD PROPERTY. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|