| Plan Review Notes For Permit 01081323 |
| Permit Number |
01081323 |
|
| Review Stop |
FS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-27 00:00:00 | 1) HYDRAULIC CALCULATIONS INDICATES | | | THAT THE TRAILER CONSTRUCTION IS | | | NON-COMBUSTIBLE. PLEASE BE ADVISED | | | THAT TYPE VI CONSTRUCTION IS NOT | | | NON-COMBUSTIBLE. | | | 2) EXECEPTION B NOTED ON THE PLANS | | | INDICATES NON-COMBUSTIBLE OR LIMITED | | | COMBUSTIBLE MATERIAL. PLEASE BE | | | ADVISED THAT AGAIN THE TRAILER IS | | | TYPE VI CONSTRUCTION LOCATED IN THE | | | CITY FIRE LIMITS. PLEASE BE ADVISED | | | THAT CERTAIN EXCEPTIONS FOR 13D SYSTEMS | | | MAY NOT APPLY SINCE THE CONSTRUCTION | | | IS TYPE VI. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|