2001-10-25 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.TONNAGE OF EXISTING AHU-1.
  
 2.CFM OF NEW SUPPLY DROP IN THE WAX
 MOLD ROOM.
  
 3.SUBMIT INFORMATION ON FUME EXHAUST
 HOOD.(CFM OF EXHAUST FAN)
  
 4.PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.