Plan Review Notes
Plan Review Notes For Permit 01081308
Permit Number 01081308
Review Stop P
Sequence Number 1
Notes
Date Text
2001-10-03 00:00:00DENIED
 REFERENCE: SPC-94
  
 PLEASE PROVIDE INFORMATION ON TWO
 DOUBLESINKS SHOWN ON PAGES A-2 AND E-1.
 INDI- CATE IF THEY COMPLY WITH FACBC-97
 SEC 4.24.
 PLEASE PROVIDE A SANITARY AND WATER
 RISER DIAGRAM SHOWING WHERE THE SYSTEMS
 WILL BE TIED INTO EXISTING LINES. SHOW
 PIPE SIZE AND VENTING. ALSO SHOW WATER
 HAMMER ARRESTORS SIZED AND LOCATED BY
 MANUFACTURE INSTALLATION INSTRUCTIONS
 WH-PDI 201.
  
 REVIEW BY KEN STEVENS
 (561) 569-8096 EXT. 8377