| Plan Review Notes For Permit 01081308 |
| Permit Number |
01081308 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-09-18 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS NEED MORE | | | FOR COMPLETE REVIEW/ | | | PLEASE SHOW LIGHTING,EXIT LTS, EM LTS, | | | ETC. EXISTING? NEW? | | | | | | 2)NOTE: PLEASE NOTE THAT OUTLET SPACING | | | TO MEET LOCAL CODE. 210-50 | | | EVERY 12' IN STUDIO`S AND EVERY 20' IN | | | STORAGE AREAS. | | | | | | 3)NOTE: PLEASE NOTE THAT ALL ELECTRICAL | | | DEVICES NEED TO HAVE BRANCH CIRCUIT #`S | | | SHOWN ON PLANS AND CORRELATE WITH | | | PANEL SCHEDULES TO BE SUBMITTED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|