2001-09-18 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT PLANS NEED MORE
 FOR COMPLETE REVIEW/
 PLEASE SHOW LIGHTING,EXIT LTS, EM LTS,
 ETC. EXISTING? NEW?
  
 2)NOTE: PLEASE NOTE THAT OUTLET SPACING
 TO MEET LOCAL CODE. 210-50
 EVERY 12' IN STUDIO`S AND EVERY 20' IN
 STORAGE AREAS.
  
 3)NOTE: PLEASE NOTE THAT ALL ELECTRICAL
 DEVICES NEED TO HAVE BRANCH CIRCUIT #`S
 SHOWN ON PLANS AND CORRELATE WITH
 PANEL SCHEDULES TO BE SUBMITTED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372