2001-09-18 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01081308
 1703 S LAKE AV
 CONT: WOOLEMS, INC
 PHONE : 835-0401
  
 SBC= 1997 STANDARD BUILDING CODE
  
 1)- GENERAL NOTES CORRECTION 1997
 STANDARD BUILDING CODE
  
 2)- SHEET A-6 "C" DISCREPANCY B/A-6 &
 C/A-6, C-CHANEL BOTH DETAILS INDICATE
 THAT THE CUT SECTION IS FOR THE SAME
 ROOM, BOTH DIRECTIONS? ROOM #110 IS NOT
 INDICATED ON A-2?
 3)- NOTE A-6 SEC "C" 12"X 6" LAG BOLTS?
 4)- THE SAME SECTION AS ABOVE IS TO BE
 DESIGNED FOR 125 LBS/SQ FT. LIGHT STOR-
 AGE SBC TABLE 1604.1. IF NOT USED FOR
 STORAGE, VERTICAL ACCESSIBILITY WILL
 BE AN ISSUE!
 5)- SEC "B" OF A-6 ENGINEER OF RECORD TO
 APPROVE THE ADDITIONAL WEIGHT OF AIR
 HANDLER #2, THE ATTACHMENT TO THE ROOF
 FRAMING MEMBERS .
 6)- SHEET A-2 CUT SECTION 1/A-4.THE
 APPLICATION INDICATES THAT ENCLOSING THE
 MATERIAL STORAGE YARD W/ CONCRETE BLOCK
 THERE IS NO FOUNDATION PLAN, DETAILS FOR
 REBAR, COLUMNS OR BEAM.
 7)- THE PLANS ALSO INDICATE A FOOTING
 F-1 TB-1 COLUMN, A NEW WF 8X21 STEEL
 BEAM, IS THIS AREA TO BE INCLUDED IN
 THIS PERMIT? IF SO NOT ENOUGH INFORMA-
 TION TO DO A REVIEW!!!
  
 BUILDING PLAN EVIEW