| Plan Review Notes For Permit 01081308 |
| Permit Number |
01081308 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-09-18 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01081308 | | | 1703 S LAKE AV | | | CONT: WOOLEMS, INC | | | PHONE : 835-0401 | | | | | | SBC= 1997 STANDARD BUILDING CODE | | | | | | 1)- GENERAL NOTES CORRECTION 1997 | | | STANDARD BUILDING CODE | | | | | | 2)- SHEET A-6 "C" DISCREPANCY B/A-6 & | | | C/A-6, C-CHANEL BOTH DETAILS INDICATE | | | THAT THE CUT SECTION IS FOR THE SAME | | | ROOM, BOTH DIRECTIONS? ROOM #110 IS NOT | | | INDICATED ON A-2? | | | 3)- NOTE A-6 SEC "C" 12"X 6" LAG BOLTS? | | | 4)- THE SAME SECTION AS ABOVE IS TO BE | | | DESIGNED FOR 125 LBS/SQ FT. LIGHT STOR- | | | AGE SBC TABLE 1604.1. IF NOT USED FOR | | | STORAGE, VERTICAL ACCESSIBILITY WILL | | | BE AN ISSUE! | | | 5)- SEC "B" OF A-6 ENGINEER OF RECORD TO | | | APPROVE THE ADDITIONAL WEIGHT OF AIR | | | HANDLER #2, THE ATTACHMENT TO THE ROOF | | | FRAMING MEMBERS . | | | 6)- SHEET A-2 CUT SECTION 1/A-4.THE | | | APPLICATION INDICATES THAT ENCLOSING THE | | | MATERIAL STORAGE YARD W/ CONCRETE BLOCK | | | THERE IS NO FOUNDATION PLAN, DETAILS FOR | | | REBAR, COLUMNS OR BEAM. | | | 7)- THE PLANS ALSO INDICATE A FOOTING | | | F-1 TB-1 COLUMN, A NEW WF 8X21 STEEL | | | BEAM, IS THIS AREA TO BE INCLUDED IN | | | THIS PERMIT? IF SO NOT ENOUGH INFORMA- | | | TION TO DO A REVIEW!!! | | | | | | BUILDING PLAN EVIEW | | | JIM WITMER | | | (561) 659-8096 X 8412 |
|