| Plan Review Notes For Permit 01081277 |
| Permit Number |
01081277 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-28 00:00:00 | ******************PROVISO*************** | | | | | | ATTIC ACCESS SHALL COMPLY WITH 1997 SMC | | | 304.4.1, ACCESS OPENING SHALL BE NO | | | LESSTHAN 22" X 36" CONTINUOUS FROM THE | | | OPENING TO THE EQUIPMENT AND ITS | | | CONTROLS. | | | | | | MUST ALSO HAVE A LIGHT ON SERVICE SIDE | | | OF EQUIPMENT CONTROLED BY A SWITCH AT | | | OPENING, A DISCONNECT SWITCH AND A | | | 110-120 VOLT A/C GROUNDING TYPE | | | CONVENIENCE OUTLET. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|