| 2002-06-14 00:00:00 | PROVISO:MECHANICAL PERMIT 01090348 | | | | | | BALANCED RETURN AIR - 2001 FBC(M) 601.4 | | | RETURN AIR SHALL BE EQUAL TO SUPPLY | | | AIR BY MEANS OF AIR TRANSFER OR A RETURN | | | AIR (JUMPER). | | | | | | SHOULD DRYER BE A GAS APPLIANCE - | | | SHOW COMPLIANCE FOR COMBUSTION AIR AS | | | PER 2001 FBC(M) CHAPTER 7. | | | | | | SMOKE DETECTORS SHALL BE INSTALLED IN | | | SUPPLY SYSTEMS WITH A DESIGN CAPACITY | | | GREATER THAN 2,000 CFM, IN THE SUPPLY | | | AIR DUCT. 2001 FBC(M) 606.2.1 | | | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTORS | | | WITH NOTIFICATION TO ALARM/STOBE OR AREA | | | SMOKE DETECTORS. 2001 FBC(M) 606.4.1 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|