Plan Review Notes
Plan Review Notes For Permit 01081199
Permit Number 01081199
Review Stop R
Sequence Number 1
Notes
Date Text
2001-09-22 00:00:00************BUILDING PROVISO************
  
 1) THE HORIZONTAL MULLION ABOVE THE 12FT
 SLIDING GLASS DOOR EXCEEDS THE ACCEPTED
 VALUES LISTED IN THE PRODUCT APPROVALS
 THAT WERE SUBMITTED. PLEASE PROVIDE
 PRODUCT APPROVALS OR ENGINEERING FOR THE
 SLIDING GLASS DOOR/WINDOW ASSEMBLY.
  
 2) THE PRODUCT APPROVALS SUBMITTED FOR
 THE SINGLE HUNG WINDOWS EXPIRED PRIOR TO
 PERMIT APPLICATION. PLEASE PROVIDE
 CURRENT PRODUCT APPROVALS FOR SH WINDOWS