| Plan Review Notes For Permit 01081166 |
| Permit Number |
01081166 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-10-09 00:00:00 | ************** UNSAT ****************** | | | | | | PLEASE NOTE THAT NOT ALL NOTES FROM | | | FIRST REVIEW WERE ADDRESSED. PLEASE SEE | | | THE FOLLOWING NOTES. | | | | | | 1)NOTE: PLEASE NOTE THAT NOW A NEW | | | ELECTRICAL RISER DIAGRAM IS BEING SUB- | | | -MITTED? PLEASE NOTE THAT LOAD CALCS DO | | | NOT SHOW WATTS/ PER SQ FT PER 220? | | | PLEASE NOTE THAT A 400AMP SERVICE IS | | | BEING INSTALLED W/ 200AMPS WORTH OF | | | WIRE AND LOAD ALREADY AT 192AMPS.??? | | | PLEASE CLARIFY AND SHOW. | | | | | | 2)NOTE: PLEASE NOTE THAT BRANCH CIRCUIT | | | #`S ARE STILL NOT SHOWN ON PLANS ,THAT | | | CORRELATE WITH PANEL SCHEDULES. | | | | | | 3)NOTE: PLEASE CLARIFY WHICH OUTLETS | | | INFRONT ARE SHOW WINDOW AND WALL OUTLETS | | | ?? PLEASE CLARIFY. | | | | | | 4)NOTE:PLEASE CLARIFY SIGN CIRCUIT PER | | | 600-5A? | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|