Plan Review Notes
Plan Review Notes For Permit 01081166
Permit Number 01081166
Review Stop E
Sequence Number 2
Notes
Date Text
2001-10-09 00:00:00************** UNSAT ******************
  
 PLEASE NOTE THAT NOT ALL NOTES FROM
 FIRST REVIEW WERE ADDRESSED. PLEASE SEE
 THE FOLLOWING NOTES.
  
 1)NOTE: PLEASE NOTE THAT NOW A NEW
 ELECTRICAL RISER DIAGRAM IS BEING SUB-
 -MITTED? PLEASE NOTE THAT LOAD CALCS DO
 NOT SHOW WATTS/ PER SQ FT PER 220?
 PLEASE NOTE THAT A 400AMP SERVICE IS
 BEING INSTALLED W/ 200AMPS WORTH OF
 WIRE AND LOAD ALREADY AT 192AMPS.???
 PLEASE CLARIFY AND SHOW.
  
 2)NOTE: PLEASE NOTE THAT BRANCH CIRCUIT
 #`S ARE STILL NOT SHOWN ON PLANS ,THAT
 CORRELATE WITH PANEL SCHEDULES.
  
 3)NOTE: PLEASE CLARIFY WHICH OUTLETS
 INFRONT ARE SHOW WINDOW AND WALL OUTLETS
 ?? PLEASE CLARIFY.
  
 4)NOTE:PLEASE CLARIFY SIGN CIRCUIT PER
 600-5A?
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372