| Plan Review Notes For Permit 01081166 |
| Permit Number |
01081166 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-30 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT ALL BRANCH | | | CIRCUIT #`S NEED TO BE SHOWN ON PLANS | | | AND CORRELATE W/ PANEL SCHEDULE THAT | | | NEEDS TO BE SUBMITTED. | | | | | | 2)NOTE: PLEASE SHOW ELECTRICAL | | | EQUIPMENTAND/OR EXSITING ELEC. | | | | | | 3)NOTE: PLEASE NOTE MISSING OUTLETS FOR | | | SHOW WINDOWS PER 210-62 AND 220-3B-7 | | | | | | 4)NOTE: PLEASE NOTE MISSING SIGN | | | CIRCUITPER 220-3B-6 AND 600-5A | | | | | | 5)NOTE: PLEASE CLARIFY LIGHTING? NONE | | | SHOWN? EXISTING? PLEASE SHOW | | | | | | 6)NOTE: PLEASE NOTE OUTLET SPACING TO | | | MEET LOCAL CODE. 210-50 | | | 12'OFFICE AND 20' OF OTHER AREAS. | | | | | | 7)NOTE: PLEASE NOTE THAT NO EXIT | | | LIGHTING AND/OR EMERGENCY LIGHTING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|