| Plan Review Notes For Permit 01081073 |
| Permit Number |
01081073 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-10-02 00:00:00 | APPROVED WITH PROVISO: | | | 1-FLOOD ZONE AO. WILL NEED TO PROVIDE | | | ELEVATION CERTIFICATE. | | | 2-PROVIDE ADDITIONAL BORINGS FOR EACH | | | STRUCTURE AS RECOMMENDED ON THE PRE- | | | LIMINARY SUBSURFACE STUDY. | | | 3-ENGINEER OF RECORD TO FILL OUT THE | | | DESIGN CERTIFICATION FOR BUILDING | | | CODE COMPLIANCE FORM. | | | 4-PROVIDE CERTIFICATION FOR 2 HR FIRE | | | RATED CONCRETE BLOCK. SEC 709.3 SBC/97 | | | | | | | | | | | | | | | | | | NOTES: | | | -DRAWINGS TO BE FILED UNDER PERMIT # | | | 01081073. | | | -THESE COMMENTS APPLY TO PERMIT #S: | | | 01081073, 01081075, 01081077, 01081078, | | | 01081081 AND 01081083. |
|