2001-09-24 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT IF THE SHOW
 WINDOW WAS THE ONLY ISSUE, THE PLANS
 COULD HAVE BEEN REDLINED.
 PLEASE NOTE THAT ALL CHANGES TO SIGNED
 AND SEALED PLANS, ARE TO BE DONE BY THE
 ENGINEER OF RECORD PER FS/ FAC. 471.025
  
 2)NOTE: PLEASE NOTE THAT 600-5, LETTER
 MENTIONS TENANT AJACENT TENANTS,??
 PLEASE CALRIFY HOW THIS MEETS 600-5.
  
 3)NOTE: PLEASE NOTE THAT THE LOAD CALCU-
 -LATIONS THAT WERE SUBMITTED ON SHEET 6
 WERE NOT COMPLETE AND SHOWN PER ART220.
 PLEASE SHOW.215-5 TRACK LIGHTING 220-12B
 NOTE CIRCUIT ADDED FOR SHOW WINDOW, NOT
 SIGNED PER ENG OF REC.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE NOTE THAT PLANS WERE
 COMING BACK FOR OTHER COMMENTS.