| Plan Review Notes For Permit 01081013 |
| Permit Number |
01081013 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-09-24 00:00:00 | ***************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE THAT IF THE SHOW | | | WINDOW WAS THE ONLY ISSUE, THE PLANS | | | COULD HAVE BEEN REDLINED. | | | PLEASE NOTE THAT ALL CHANGES TO SIGNED | | | AND SEALED PLANS, ARE TO BE DONE BY THE | | | ENGINEER OF RECORD PER FS/ FAC. 471.025 | | | | | | 2)NOTE: PLEASE NOTE THAT 600-5, LETTER | | | MENTIONS TENANT AJACENT TENANTS,?? | | | PLEASE CALRIFY HOW THIS MEETS 600-5. | | | | | | 3)NOTE: PLEASE NOTE THAT THE LOAD CALCU- | | | -LATIONS THAT WERE SUBMITTED ON SHEET 6 | | | WERE NOT COMPLETE AND SHOWN PER ART220. | | | PLEASE SHOW.215-5 TRACK LIGHTING 220-12B | | | NOTE CIRCUIT ADDED FOR SHOW WINDOW, NOT | | | SIGNED PER ENG OF REC. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. PLEASE NOTE THAT PLANS WERE | | | COMING BACK FOR OTHER COMMENTS. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|