| Plan Review Notes For Permit 01081013 |
| Permit Number |
01081013 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-09-18 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE: PLEASE NOTE THAT COMPLETE LOAD | | | CALCUALTIONS WERE NOT SUBMITTED> PLEASE | | | SHOW! INCLUDING SQ FTETC. PER 220 | | | PLEASE SHOW TRACK LIGHTING PER 220-12B | | | | | | 2)NOTE: PLEASE NOTE MISSING SHOW WINDOW | | | RECEPTS PER 210-62/ LOADS PER 220-12A | | | | | | 3)NOTE: PLEASE NOTE/CLARIFY SIGN CIRCUIT | | | PER 600-5. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|