2001-09-18 00:00:00************** UNSAT *******************
  
 1)NOTE: PLEASE NOTE THAT COMPLETE LOAD
 CALCUALTIONS WERE NOT SUBMITTED> PLEASE
 SHOW! INCLUDING SQ FTETC. PER 220
 PLEASE SHOW TRACK LIGHTING PER 220-12B
  
 2)NOTE: PLEASE NOTE MISSING SHOW WINDOW
 RECEPTS PER 210-62/ LOADS PER 220-12A
  
 3)NOTE: PLEASE NOTE/CLARIFY SIGN CIRCUIT
 PER 600-5.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  