| 2001-10-23 00:00:00 | DENIED |
| | REFERENCE: SPC-94 - FACBC-97 |
| | |
| | 1) FULL SETS OF PLANS REQUIRED. PAGE A-2 |
| | NOT INCLUDED IN RESUBMITED SET, AND DEMO |
| | PAGES NEED TO BE INSERTED. PLEASE SUBMIT |
| | FULL SETS FOR REVIEW. |
| | 2) PAGE A-1, RM 111. DOOR OUT OF ROOM |
| | SO AS NOT TO SWING INTO TURNING RADIUS. |
| | FACBC-97 4.22.3 |
| | 3) PAGE A-1 LUNCH ROOM. CLEAR FLOOR |
| | SPACE FOR PARALLEL, FIXTURE MUST CENTER |
| | ON CLEAR FLOOR SPACE. SINK ONLY 18" INTO |
| | CLEAR FLOOR SPACE. FRONTAL APPROACH IS |
| | REQUIRED. PLEASE SHOW DETAIL AND SHOW |
| | COMPLIANCE WITH ALL DETAILS OF SEC 4.24 |
| | 4) PLEASE SHOW WATER RISER DIAGRAM AS |
| | REQUESTED IN PREVIOUS PLAN REVIEW. NOTE |
| | #7 IN PLUMBING NOTES ON PAGE E-1 CALLS |
| | FOR AIR CHAMBERS, BUT NOTE BY SANITARY |
| | RISER CALLS FOR AIR HAMMER ARRESTORS. IF |
| | WATER HAMMER ARRESTORS ARE USED PLEASE |
| | NOTE IN NOTE #7 AND SHOW THEM IN WATER |
| | RISER DIAGRAM. PLACEMENT AND SIZE SHALL |
| | BE PER MANUFACTURES INSTALLATION INSTRU- |
| | CTIONS AND WH-PDI 201. PLACEMENT SHALL |
| | BE CLOSE TO FIXTURE NOT AT TOP OF DROP. |
| | 5) PAGE E-1 NOTE #4. FROM PREVIOUS RE- |
| | VIEW SHOW CONDENSATE SYSTEM SO PLUMBING |
| | CONTRACTOR CAN INSTALL. SHOW TERMINATION |
| | OF CONDENSATE. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT. 8377 |