Plan Review Notes
Plan Review Notes For Permit 01080985
Permit Number 01080985
Review Stop P
Sequence Number 3
Notes
Date Text
2001-11-13 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) THREE COMPARTMENT SINK TO DRAIN INDIR
 ECTLY TO A FLOOR SINK PER SPC SEC 804.1.
  
 2) HAND SINK TO DRAIN DIRECTLY INTO SAN-
 ITARY NOT TO FLOOR SINK.
  
 3) VENT REQUIRED AT UPSTREAM OF EACH
 BRANCH, (BEFORE 1ST FLOOR SINK), PER
 SPC SEC 921.4.2.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377