| Plan Review Notes For Permit 01080985 |
| Permit Number |
01080985 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-09-04 00:00:00 | DENIED | | | REFERENCE: SPC-94 - | | | | | | 1) PAGES A-6 & P-1, HUB DRAINS NOT ALLOW | | | ED. INDIRECT WASTE TO DRAIN TO A FLOOR | | | SINK PER SPC-94 SECTIONS 804.5 AND 807. | | | | | | 2) WATER HEATER TO BE READILY ACCESSIBLE | | | PER SPC-94 SECTION 501.7. IF ON A SHELF, | | | A PERMINATE SHIPS LADDER AND A PERMINATE | | | WORK PLATFORM ARE REQUIRED. THE WORK | | | AREA SHALL BE PROVIDED THAT IS A MINIMUM | | | OF 30"WIDE FROM THE BASE OF THE HEATER. | | | SMC-97 SECTION 304.4.1. | | | | | | 3) PAGE A-6, WATER FILTRATION SYSTEM | | | SHALL BE NSF APPROVED PER SPC SEC. 615.1 | | | 615.2. PLEASE SUBMIT MANUFACTURE INFO. | | | | | | 4) PAGE P-1, 4" HUB DRAIN, 3" HUB DRAIN, | | | AND 3" HUB DRAIN NOT ALLOWED. SEE COM- | | | MENT #1. | | | | | | 5) 3" VENT THRU ROOF REQUIRED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|