Plan Review Notes
Plan Review Notes For Permit 01080985
Permit Number 01080985
Review Stop P
Sequence Number 1
Notes
Date Text
2001-09-04 00:00:00DENIED
 REFERENCE: SPC-94 -
  
 1) PAGES A-6 & P-1, HUB DRAINS NOT ALLOW
 ED. INDIRECT WASTE TO DRAIN TO A FLOOR
 SINK PER SPC-94 SECTIONS 804.5 AND 807.
  
 2) WATER HEATER TO BE READILY ACCESSIBLE
 PER SPC-94 SECTION 501.7. IF ON A SHELF,
 A PERMINATE SHIPS LADDER AND A PERMINATE
 WORK PLATFORM ARE REQUIRED. THE WORK
 AREA SHALL BE PROVIDED THAT IS A MINIMUM
 OF 30"WIDE FROM THE BASE OF THE HEATER.
 SMC-97 SECTION 304.4.1.
  
 3) PAGE A-6, WATER FILTRATION SYSTEM
 SHALL BE NSF APPROVED PER SPC SEC. 615.1
 615.2. PLEASE SUBMIT MANUFACTURE INFO.
  
 4) PAGE P-1, 4" HUB DRAIN, 3" HUB DRAIN,
 AND 3" HUB DRAIN NOT ALLOWED. SEE COM-
 MENT #1.
  
 5) 3" VENT THRU ROOF REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377