| Notes |
| Date |
Text |
| 2001-09-06 00:00:00 | ******************DENIED**************** | | | | | | | | | PLEASE PROVIDE OUTSIDE AIR CALCULATIONS | | | AS PER ASHRAE 62-89 AS WELL AS AIR | | | BALANCE SCHEDULE TO SHOW COMPLIANCE | | | WITH 1997 SMC 501.2. | | | | | | CONDENSATE SHALL NOT GO TO THE SANITARY. | | | MUST COMPLY WITH AMMENDED 1994 SPC 804.3 | | | #2 OR 3. | | | | | | ADDITIONAL PERMITS REQUIRED FOR HOODS, | | | FIRE SUPRESSION, AND WALK-IN COOLERS. | | | PLEASE PROVIDE PLANS AND MANUFACTURER | | | SUBMITTAL DATA WITH PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|