| Plan Review Notes For Permit 01080985 |
| Permit Number |
01080985 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-30 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS ARE | | | MISSING REQ`D SIGN PER 600-5 AND LOADS | | | SHOWN PER 220-3B-6. | | | | | | 2)NOTE: PLEASE NOTE MISSING OUTLET(S) | | | FOR SHOW WINDOW 210-62 AND LOADS PER | | | 220-12A,220-3B-7 | | | | | | 3)NOTE: PLEASE NOTE THAT NO INFORMATION | | | SHOWN FOR MAIN SERVICE COMING IN? | | | OCP OF MAIN DISC? AIC RATING? | | | PLEASE NOTE THAT RISER SHOWS AND EQUIP- | | | -MENT GROUNDING CONDUCTOR FROM METER TO | | | MAIN? PLEASE NOTE THAT THIS WOULD BE | | | PARALELLING THE NEUTRAL. | | | | | | 4)NOTE: PLEASE NOTE THAT LOADS SHOWN | | | ON PANEL SCHEDULE ARE SHOWN AT CONNECTED | | | AMPERAGES? PLEASE SHOW LOAD CALCULATIONS | | | AND ALL CONTINUOUS LOADS AT 125% | | | LIGHTING) PER 220 AND 230-42/215-3 | | | | | | 5)NOTE: PLEASE NOTE THAT PLANS ARE NOT | | | SHOWING GUTTER AT SAME LOCATION AS PANEL | | | ? PLEASE CLARIFY. A/C DISCONNECTA ARE | | | SHOWN AS BEING TAPPED CONDUCTORS AND | | | NEED TO FALL UNDER 240-21 FOR TAPPED | | | CONDUCTORS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REAVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|