Plan Review Notes
Plan Review Notes For Permit 01080985
Permit Number 01080985
Review Stop E
Sequence Number 1
Notes
Date Text
2001-08-30 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT PLANS ARE
 MISSING REQ`D SIGN PER 600-5 AND LOADS
 SHOWN PER 220-3B-6.
  
 2)NOTE: PLEASE NOTE MISSING OUTLET(S)
 FOR SHOW WINDOW 210-62 AND LOADS PER
 220-12A,220-3B-7
  
 3)NOTE: PLEASE NOTE THAT NO INFORMATION
 SHOWN FOR MAIN SERVICE COMING IN?
 OCP OF MAIN DISC? AIC RATING?
 PLEASE NOTE THAT RISER SHOWS AND EQUIP-
 -MENT GROUNDING CONDUCTOR FROM METER TO
 MAIN? PLEASE NOTE THAT THIS WOULD BE
 PARALELLING THE NEUTRAL.
  
 4)NOTE: PLEASE NOTE THAT LOADS SHOWN
 ON PANEL SCHEDULE ARE SHOWN AT CONNECTED
 AMPERAGES? PLEASE SHOW LOAD CALCULATIONS
 AND ALL CONTINUOUS LOADS AT 125%
 LIGHTING) PER 220 AND 230-42/215-3
  
 5)NOTE: PLEASE NOTE THAT PLANS ARE NOT
 SHOWING GUTTER AT SAME LOCATION AS PANEL
 ? PLEASE CLARIFY. A/C DISCONNECTA ARE
 SHOWN AS BEING TAPPED CONDUCTORS AND
 NEED TO FALL UNDER 240-21 FOR TAPPED
 CONDUCTORS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REAVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372