| Notes |
| Date |
Text |
| 2001-09-28 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) PAGE P1, KEY NOTE #2, ALSO PAGE P2, | | | WATER ISOMETRIC. BACKFLOW IS REQUIRED ON | | | WATER SERVICE TO THIS BUILDING TO PRO- | | | TECT THE POTABLE WATER FROM THE COSMO- | | | TOLOGY BUILDING. | | | | | | 2) PAGE P2, WATER ISOMETRIC. AIRCHAMBERS | | | ARE STILL SHOWN. PLEASE REMOVE IF NOT | | | USING AIR CHAMBERS. WATER HAMMER ARREST- | | | ORS SHALL BE INSTALLED PER MANUFACTURES | | | INSTALLATION INSTRUCTIONS AND WH-PDI 201 | | | AND NOT AT THE TOP OF THE DROP AS SHOWN. | | | SEE ATTACHED SHEET FROM WH-PDI 201 FOR | | | EXAMPLE OF LOCATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|