| Plan Review Notes For Permit 01080756 |
| Permit Number |
01080756 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-10-02 00:00:00 | ******************PROVISO*************** | | | | | | | | | EXISTING RTU FRESH AIR INTAKE SHALL BE | | | A MINIMUM OF 10' FROM ANY EXHAUST | | | TERMINATING AT THE ROOF. | | | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | SHALL HAVE NOTIFICATION TO ALARM/STROBE | | | IN NORMALLY OCCUPIED AREAS AS PER NFPA | | | 90A 4-4.4.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|