| 2001-08-31 00:00:00 | DENIED |
| | REFERENCE: SPC-94 - FCABC-97 |
| | |
| | 1) PAGES A1 & A2, PER FCABC-97 SECTION |
| | 4.17.3, EXCEPTION: NEW CONSTRUCTION (2), |
| | THE ACCESSIBLE WATER CLOSET SHALL BE |
| | LOCATED IN THE CORNER, DIAGONAL TO THE |
| | DOOR. |
| | |
| | 2) PAGE A1 & A2, PER FCABC-97 SECTION |
| | 4.22.5, IF URNALS ARE PROVIDED, THEN AT |
| | LEAST ONE SHALL COMPLY WITH 4.18. |
| | |
| | 3) PAGE P1, KEY NOTES #2, ALSO PAGE P2, |
| | WATER ISOMETRIC, BACKFLOW IS REQUIRED |
| | ON WATER SERVICE. |
| | |
| | 4) PAGE P1, KEY NOTES #'S 10 & 11, |
| | PRESSURE RELIEF LINE ONLY REQUIRED TO BE |
| | 3/4", AND PAN DRAIN LINE IS REQUIRED TO |
| | BE 1". |
| | |
| | 5) PAGE P1, KEY NOTES #'S 7 & 8 SHOULD |
| | BE REVERSED. |
| | |
| | 6) PAGE P2, GENERAL NOTES #16, AIR CHAM- |
| | BERS SHALL COMPLY WITH SPC-94 SECTIONS |
| | 607.8.2 & 607.8.3 (ACCESSABLE AND RE- |
| | CHARGEABLE). IF WATER HAMMER ARRESTORS |
| | ARE USED, THEY SHALL COMPLY WITH MANU- |
| | FACTURE'S INSTALLATION INSTRUCTIONS WITH |
| | RESPECT TO SIZE AND LOCATION. SEE PDI- |
| | WH 201 ALSO. |
| | |
| | 7) PAGES A1, A2, P1 & P2. FLOOR DRAINS |
| | ARE REQUIRED IN PUBLIC BATH ROOMS. ALSO |
| | THEY ARE REQUIRED TO HAVE TRAP PRIMERS |
| | TO MAINTAIN WATER SEAL. SPC-94 SECTION |
| | 409.4.1.1. |
| | |
| | 8) PAGES A1, A2 & P1, SINK IN DISPENSARY |
| | TO COMPLY WITH FACBC-97 SECTION 4.24 |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT. 8377 |