| 2001-08-21 00:00:00 | *************** UNSAT ************ |
| | |
| | 1)NOTE: PLEASE NOTE THAT PLANS SUBMITTED |
| | FOR ELECTRICAL REVIEW WERE NOT CLEAR |
| | ENOUGH IN DETAIL FOR PROPER REVIEW. |
| | PLEASE SUBMIT PLANS FOR ELECTRICAL |
| | LAYOUTS. PLEASE NOTE THAT PLANS NEED TO |
| | BE RE-DRAWN UNDER COUNTY-WIDE AND CITY- |
| | WIDE ADMINISTRATIVE CODE 104.2.7. |
| | |
| | PLEASE NOTE THAT THE FOLLOWING ARE SOME |
| | ITEMS THAT COULD BE SEEN ON PAGE 1 OF 2 |
| | OF THE ELEC SUBMITTED. |
| | |
| | 1) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | PLEASE SHOW DOORS TO ALL BEDROOMS. |
| | |
| | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 3) NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210-8-A-6. |
| | |
| | 4) PLEASE NOTE EITHER MISSING EGRESS |
| | LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| | PER 210-70 OF THE NEC. |
| | PLEASE DRAW IN SWITCH LEGS AND SHOW |
| | DEVICES THAT ARE BEING USED. |
| | |
| | 5)NOTE: PLEASE PROVIDE CLARIFICATION ON |
| | PANELS AND IF NEW EQUIPMENT IS BEIING |
| | INSTALLED? EXISTING? RE-PULLING |
| | CONDUCTORS?? |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |