| 2001-11-01 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 01080716 |
| | 2815 N FLAGLER DR |
| | CONT: CASTLE FLORIDA BUILD |
| | TEL: 272-1207 |
| | |
| | SBC= 1997 STANDARD BUILDING CODE |
| | SBC*= AMENDMENTS/ STANDARD BUILDING CODE |
| | |
| | 1)- SHEET A-4: |
| | A) RECEPTION ROOM HAS (2) SETS OF DOUB- |
| | LE DOORS, D-14 & E.R. (EXISTING DOOR), |
| | WILL EXISTING DOOR HAVE PANIC HARDWARE. |
| | B) DOOR D-14 NOTE 32X10 PT HEADER, |
| | TYPE II CONSTRUCTION, NO WOOD ALLOWED IN |
| | EXTERIOR WALS. |
| | C) SBC 1606.2.6.2 COMPONENTS & CLADDING |
| | WILL REQUIRE (2 COPIES) OF PRODUCT TEST- |
| | ING REPORTS FOR ALL OPENINGS & ROOFING |
| | ASSEMBLIES INCLUDED: |
| | WINDOWS |
| | DOORS |
| | ROOFING ASSEMBLIES |
| | STORM SHUTTERS |
| | THE CITY ACCEPTS S.B.C.C.I. AND DADE |
| | COUNTY PRODUCT TESTING REPORTS. |
| | D) COFFERED CEILING SECTION A 4-5 THERE |
| | IS NO ACTUAL DETAIL WITH ATTACHMENT TO |
| | THE BAR JOIST OR WALL NOR IS THERE INFO |
| | FOR TYPE OF MATERIAL, SPACING ? |
| | |
| | SHEETA-5: |
| | A) SEC. A-A INDICATES GYP. BD. ON HAT |
| | CHANNEL HUNG FROM THE BAR JOIST, ISN'T |
| | THE HI-HAT ACTUALLY HUNG FROM 1 1/2 C |
| | CHANNEL,WITH THE HI HAT TIE WIRED FROM |
| | THE C CHANNEL? HANGING WIRE SIZE, |
| | SPACING OF C CHANNEL & OF THE HI-HAT? |
| | THICKNESS OF THE GYPSUM BOARD? |
| | |
| | MISSING INFORMATION SBC TABLE 803.3 |
| | MINIMUM INTERIOR FINISH CLASSIFICATION. |
| | |
| | CONTACTOR SHALL HAVE THE PLANS REVIEWED |
| | FOR ADDITIONAL FEES COUNTY IMPACT FEES. |
| | |
| | BUILDING PLAN REVIEW |