Plan Review Notes
Plan Review Notes For Permit 01080716
Permit Number 01080716
Review Stop P
Sequence Number 1
Notes
Date Text
2001-09-10 00:00:00DENIED
  
 REFERENCE: SPC-94
  
 1) PAGE A7, PLEASE PROVIDE ROOF DRAINAGE
 CALCULATIONS FOR NEW ROOF AREAS. SIZE
 PER SPC-94 SECT 1108 & 1109. PLEASE SHOW
 PRIMARY AND SECONDARY DRAINS ON DETAIL.
  
 2) PAGE A4, PLEASE SHOW CALCULATIONS FOR
 MINIMUM FACILITIES, SPC-94 TABLE 407.
 SHOW HOW NEW BLDGS. IMPACT EXISTING FAC-
 ILITIES AND SHOW HOW THE NEW RECEPTION
 ROOM WILL BE USED. (WILL IT BE ADDING TO
 THE AMOUNT OF PEOPLE USING EXISTING FAC-
 ILITIES?)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377