| Plan Review Notes For Permit 01080716 |
| Permit Number |
01080716 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-09-04 00:00:00 | 1) STORAGE ROOM NOT FIRE RATED. SINCE | | | NO FIRE SPRINKLERS ARE PLANNED, THIS | | | ROOM IS REQUIRED TO BE AT LEAST ONE | | | HOUR FIRE RATED. PLEASE DISPLAY THIS | | | ONE THE PLANS AND CORRECT THE NON-RATED | | | DOOR TO A RATED ONE. | | | 2) ARE THE DOUBLE DOORS NOTED ER FROM | | | THE RECEPTION ROOM EQUIPPED WITH | | | PANIC HARDWARE. | | | 3) PLEASE INDICATE FLAMESPREAD RATINGS | | | FOR WALLS AND CEILINGS. | | | 4) NEW ADDITION TO COMPLY WITH | | | REQUIREMENTS FOR NEW OCCUPANCY TYPE. | | | 5) NO FIRE ALARM EQUIPMENT SHOWN. ARE | | | THERE ANY FIRE ALARM EQUIPMENT IN THE | | | BUILDING AND IF SO, WHY ARE NONE SHOWN | | | FOR THE NEW AREA. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|